Low smoke halogen free cable LSZH
Product Detailed
Related Categories:Electrical Wires
Low smoke halogen free
Low-smoke free-halogen flame-retardancy polyolefin insulated electric Wire
Using place:the high-rise civil building (except super high-rise uptown) and underground civil building(with structural area).
Specification:
1. The maximum temperature of the normal operating cable conductor or short circuit (should not persist for 5seconds).
2.70oC for low-smoke low-halogen PVC insulated type as normal operation,and not more than 160oC as short circuit.
90oC XLPE insulated type' 80oC for thermoplastic low-smoke low-halogen polyolefin insulated type,and not more than 250oC as short circuit.
No. | Testing item | Standard requirement(free-haloegn) | Standard requirement(low-haloegn) |
1 | Single vertical combustion testing for wires and cables:1)the distance from the skirt of upper bracket to charcoal part2)the distance from combustion prolongation to the skirt of upper bracket | ≥50mm ≤540mm | ≥50mm ≤540mm |
2 | Cable colligated combustion testing:the height of charcoal part | ≤2.5m | ≤2.5m |
3 | Fire resistance testing | As testing,bear rated voltage and the 2A fuse will not be melted | As testing,bear rated voltage and the 2A fuse will not be melted |
4 | PH value | ≥4.3 | ≥2.5 |
5 | Conductance | ≤10μs/mm | no requirement |
6 | Smoke density testing:minimum light-pass tate | ≥60% | ≥30% |